Verify communication – Yaskawa G7 Modbus Communication User Manual

Page 16

Advertising
background image

16

Verify Communication

The following is a quick reference guide for serial communications to the G7 drive. Make a copy of this page and check-off each item as it is

completed. For detailed information please refer to the detailed sections that follow.

1: RS-232

Communication.

1.1:

Verify that the correct cable is used to connect the controller to the G7 drive.

1.2:

Verify that the controller is set for RS-232 communication and that the communication cable is connected to the correct
communication port.

1.3:

Record the controller communication parameters.

Baud Rate

Parity

Data

Bits

Stop

Bits 1

1.4:

Record the G7 drive communication parameters (H5-02, H5-03, H5-07).

Baud Rate

Parity

Data

Bits

Stop

Bits 1

1.5:

Verify that the communication parameters match.

2: RS-422/RS-485

Communication.

2.1:

Verify that the G7 drive is connected correctly.

2.2:

Verify that the controller is set for RS-422/RS-485 communications and that the communications cable is connected to
the correct communications port.

2.3:

Record the controller communications parameters.

Baud Rate

Parity

Data

Bits

Stop

Bits 1

2.4:

Record the G7 drive communication parameters (H5-01, H5-02, H5-03, H5-07).

Baud Rate

Parity

Data

Bits

Stop

Bits 1

2.5:

Verify that the communication parameters match.

2.6:

Verify that parameter H5-07 (RTS) is set to enable.

2.7:

Verify that parameter H5-01 (Node Address) is set to the correct, unique, hexadecimal value and that it matches the
node address required by the controller.

Controller Node Address

G7 Drive Node Address

Advertising