Communication Fault (CE) Response Selection – H5-04. Select the drive operation method when a communication fault (CE)

occurs. See parameter H5-05 also.

Table 1.4 Communication Fault Response Selection – Parameter H5-04

Value

Description

0

Ramp to Stop (Fault)

1

Coast to Stop (Fault)

2

Fast Stop (Fault)

3

Alarm Only (Alarm) (Default Setting)

4

Run at D1-04 frequency



Communication Fault (CE) Detection Selection – H5-05. Selects whether the communication fault (CE) is monitored. Please note

that either B1-01 or B1-02 must also be set to a 2 (Serial Communication) for fault monitoring to occur. If the CE fault is enabled, the

G7 will flash CALL on the keypad after power up until a message is received. The drive will trip and respond according to H5-04 if

communication is lost (a message is not received) for more than 2 seconds after successful communication has been initiated.

Table 1.5 Communication Fault Detection Selection – Parameter H5-05

Value

Description

0

Disabled (Default Setting)

1 Enabled



Serial Communication Send Delay – H5-06. A delay can be inserted before the G7 drive responds to a command message. This

allows for slower communication devices to switch their transceiver state in order to get ready to receive a message. A value of 5 ~ 65

ms can be inserted, with 5 ms being the default.



RTS Control – H5-07. This parameter determines whether RTS is continually asserted (disabled) or asserted only during send

(enabled). RTS must be enabled for use with RS-485 2-wire communication.

Table 1.6 RTS Control – Parameter H5-07

Value

Description

0

Disable (always ON) (Default Setting)

1

Enable (ON only during send) (Use this setting for RS-485 2-wire systems)