Yaskawa G7 Modbus Communication User Manual

Page 68

Advertising
background image

68

Table 4.11 “L” Parameters

Access Level

Name

Address

Description

Data

Range

Unit

Default

During

Run

V/f

V/f

w/PG

OLV

FV

OLV2

0 Disabled

1

Standard Fan Cooled

2 Standard

Blower

Cooled

L1-01

0480h

Motor Overload (OL1)

Motor Selection

3 Vector

Duty

1

1

Q Q Q Q Q

L1-02

0481h

Motor Overload (OL1)

Time Constant

0.1 ~ 5.0 min

0.1 min

1.0 min

A

A

A

A

A

0

Ramp to Stop

1

Coast to Stop

2 Fast-Stop

(C1-09)

L1-03

0482h

Motor Overheat (OH3)

Alarm Selection

3 Alarm

Only

1

3

A A A A A

0

Ramp to Stop

1

Coast to Stop

L1-04

0483h

Motor Overheat (OH4)

Fault Selection

2 Fast-Stop

(C1-09)

1

1

A A A A A

L1-05

0484h

Motor Overheat Filter

Time

0.00 ~ 10.00 Sec

0.01 Sec

0.20 Sec

A

A

A

A

A

0 Disabled

1

Enabled - L2-02 Time

L2-01

0485h

Power Loss Ride Thru

Selection

2

Enabled - CPU Active

1

0

A A A A A

L2-02

0486h

Power Loss Ride Thru

Time

0.0 ~ 25.5 Sec

0.1 Sec

0.1 Sec

A

A

A

A

A

L2-03

0487h

Minimum Baseblock

Time

0.1 ~ 5.0 Sec

0.1 Sec

0.5 Sec

A

A

A

A

A

L2-04

0488h

Voltage Recovery Ramp

Time

0.0 ~ 5.0 Sec

0.1 Sec

0.3 Sec

A

A

A

A

A

L2-05

0489h

Undervoltage Detection

Level

kVA Dep.

1 VDC

kVA Dep.

A A A A A

L2-06

048Ah

KEB Decel Time

0.0 ~ 200.0 Sec

0.1 Sec

0.0 Sec

A

A

A

A

A

L2-07

048Bh

Powerloss Ride Thru

Accel Time

0.0 ~ 25.5 Sec

0.1 Sec

0.0 Sec

A

A

A

A

A

L2-08

048Ch

KEB Frequency Gain

0 ~ 300 %

1 %

100 %

A

A

A

A

A

0 Disabled

1 General

Purpose

L3-01

048Fh

Stall Prevention During

Accel Selection

2 Intelligent

1

1

A A A

L3-02

0490h

Stall Prevention During

Accel Current Level

0 ~ 200 %

1 %

150 %

A

A

A

L3-03

0491h

Stall Prevention During

Accel Constant HP Area

Current Lower Limit

0 ~ 100 %

1 %

50 %

A

A

A

0 Disabled

1 General

Purpose

2 Intelligent

L3-04

0492h

Stall Prevention During

Decel Selection

3

Enabled - Braking Resistor

1

1

Q Q Q Q Q

0 Disabled

1

Decel Time 1 (C1-02)

L3-05

0493h

Stall Prevention During

Run Selection

2

Decel Time 2 (C1-04)

1

1

A A

L3-06

0494h

Stall Prevention During

Run Current Level

30 ~ 200 %

1 %

160 %

A

A

0 Disabled

L3-11

04C7h

Overvoltage Inhibit

Selection

1 Enabled

1

0 A

A

A

L3-12

04C8h

Overvoltage Inhibit

Voltage Level

kVA Dep.

1 V

kVA Dep.

A

A

A

L4-01

0499h

Speed Agree Level

0.0 ~ 400.0 Hz

0.1 Hz

0.0 Hz

A

A

A

A

A

L4-02

049Ah

Speed Agree Width

0.0 ~ 20.0 Hz

0.1 Hz

2.0 Hz

A

A

A

A

A

L4-03

049Bh

Speed Agree Level +/-

-400.0 ~ 400.0 Hz

0.1 Hz

0.0 Hz

A

A

A

A

A

L4-04

049Ch

Speed Agree Width +/-

0.0 ~ 20.0 Hz

0.1 Hz

2.0 Hz

A

A

A

A

A

0 Stop

L4-05

049Dh

Frequency Reference

Loss Selection

1

Run at L4-06 x Previous

Reference

1

0

A A A A A

L4-06

04C2h

Frequency Reference

Loss Gain

0.0 ~ 100.0 %

0.1 %

80.0 %

A

A

A

A

A