Run/Stop and Frequency Reference

The Run/Stop and Frequency Reference commands can originate from:



Serial communication (Built-in Modbus: Keypad or R+/-, S+/- Terminals)



Keypad (Digital Operator)



Terminal Strip



Option Card

Parameter B1-01 (Run/Stop Method Selection) allows the selection of the origin of the Run/Stop command. Parameter B1-02 (Reference

Selection) allows the selection of the origin of the Frequency Reference command. The Run/Stop and Frequency Reference commands may

have different origins.

For example, the Run/Stop command may be set to Terminals (B1-01=1) while the Frequency Reference command may be set to Serial

Communication (B1-02=2).



Run/Stop Source

Table 1.7 Run/Stop Method Selection

B1-01

Operation Method Selection (Run/Stop)

0 Keypad

1

Terminal Strip (Default Setting)

2

Serial Communication (Built-in Modbus: Keypad or R+/-, S+/- Terminals)

3

Option Card (EtherNet/IP, Modbus TCP/IP, DeviceNet, Profibus DP, LonWorks, etc.)

4

Pulse Input (RP Terminal)



Frequency Reference Source

Table 1.8 Frequency Reference Source Selection

B1-02

Frequency Reference Selection

0 Keypad

1

Terminal Strip (Default Setting)

2

Serial Communication (Built-in Modbus: Keypad or R+/-, S+/- Terminals)

3

Option Card (EtherNet/IP, Modbus TCP/IP, DeviceNet, Profibus DP, LonWorks, etc.)