7.2.2 ILX69-PBM LEDs

The ILX69-PBM LEDs indicate the status information. Each LED has a specific function
during Run, configuration download, and error indications. The table below shows the
activity of each.

Power On

The PWR LED is described below.

LED

Color

State

Description

PWR

LED green

(Green)

On

Power supply for the device is on

(Off)

Off

Power supply for the device is missing

PROFIBUS System Status

The SYS PROFIBUS network status LED is described below.

LED

Color

State

Description

SYS

Duo LED yellow/green

(Green)

On

Operating system running

(Green/Yellow)

Blinking
Green/Yello
w

Second stage bootloader is waiting for firmware

(Yellow)

Static

Bootloader netX (= romloader) is waiting for second stage
bootloader

(Off)

Off

Power supply for the device is missing or hardware defect

Communication Status

The ILX69-PBM PROFIBUS DP COM LED status is described below.

LED

Color

State

Description

COM

Duo LED red/green

(Green)

On

Communication to all slaves is established

(Green)

Flashing cyclic

PROFIBUS is configured, but bus communication is not
yet released from the application

(Green)

Flashing acyclic

No configuration or faulty configuration

(Red)

Flashing cyclic

Communication to at least one slave is disconnected.

(Red)

On

Communication to all slaves is disconnected or another
serious error has occurred.
Redundant Mode: The active master was not found.