DPV1 Alarm Response
Code
Significance
Error source
Help
86 hex = REJ_INT
The alarm handler
is not initialized
Device
No DPV1 capable device configured within
the module
87 hex = REJ_SRT The alarm handler
is currently stopped
Device
No DPV1 capable slave device is in
process data exchange with the device.
Check if network is running.
88 hex = REJ_ENA The alarm that
shall be
acknowledged is
not enabled in
slave parameter
data
Host
Enable the corresponding alarm in slave
configuration data set
89 hex = REJ_NPD The alarm that
shall be
acknowledged is
not pending on a
MSAL1_Alarm_Re
s
Host
Check the parameter AlarmType and
Seq_Nr. Both must be equal to the
MSAL1_Alarm_ind parameter
9a hex =
REJ_COM
Unknown msg.b
command
Host
Correct the requested msg.b parameter of
message