ProSoft Technology ILX69-PBM User Manual

Page 74

Advertising
background image

Contents

ILX69-PBM ♦ CompactLogix or MicroLogix Platform

User Manual

PROFIBUS Master Communication Module

Page 74 of 124

ProSoft Technology, Inc.

February 4, 2015

Slave Diag Failure
This byte reflects the status of the Slave Diagnostics request.

Error
Code

Significance

Error
source

Description

0

Service could be executed
without an error

No error

No error detected.

17

No response from the
station

Slave

Check network wiring, bus address of slave, or baud rate
support.

18

Master not in the logical
token ring

Network in
general

Check master DP address or highest-station address of the
master. Examine bus wiring for short circuits.

161

Remote Address in
request service is out of
range

Application Check address parameter in diagnostics request.

Station Status_1
Slave device status information.

Bit
Offset

Member
Name

Data
Type

Description

0

Sta_Non_Exist

BOOL

No response from slave device. The slave is non-existent.

1

Sta_Not_Ready

BOOL

Slave is not ready

2

Cfg_Fault

BOOL

Slave has incorrect parameterization

3

Ext_Diag

BOOL

The extended diagnostics area is used

4

Not_Supp

BOOL

Unknown command is detected by the slave

5

Inv_Slv_Res

BOOL

Invalid slave response

6

Prm_Fault

BOOL

Last parameterization telegram was faulty

7

Master_Lock

BOOL

Slave is controlled by another master

Station Status_2
Slave device status information (continued)

Bit
Offset

Member
Name

Data
Type

Description

0

Prm_Req

BOOL

Parameter Request: Slave must be parameterized

1

Stat_Diag

BOOL

This bit remains active until all diagnostics data has been
retrieved from the slave

2

Slave_Device

BOOL

This bit is always set by the slave

3

WD_On

BOOL

Slave watchdog is activated

4

Freeze_Mode

BOOL

Freeze command active

5

Sync_Mode

BOOL

Sync command active

6

Reserved

BOOL

Reserved, set to 0

7

Deactivated

BOOL

Slave not active