ProSoft Technology ILX69-PBM User Manual

Page 89

Advertising
background image

ILX69-PBM ♦ CompactLogix or MicroLogix Platform

Contents

PROFIBUS Master Communication Module

User Manual

ProSoft Technology, Inc.

Page 89 of 124

February 4, 2015

15 hex

0000 hex

Configuration data size
too large

Too much data
transferred with the
CIP Message

Check if the overall length of
the requested command of
the CIP message and the
consistency of all length
parameters within the
requested command.

16 hex

0000 hex

Object not supported

The requested object
does not exist within
the module.

FE hex

0000 hex

Message Timeout

No answer message
was received.

FF hex

0514 hex

General Error
Non specified error
occurred

Contact technical support

FF hex

0517 hex

General Error
Unknown command

The value in the
requested command is
unknown

The value in requested
command must be initialized

Slave Diagnostic

Code

Significance

Error source

Help

0

No error detected

N/A

N/A

17

No response from
the station

Slave

Check network wiring, check bus address of
slave or baud rate support

18

Master not into the
logical token ring

Network in general

Check ILX69-PBM address or highest-station-
address of the master. Examine bus wiring for
bus short circuits.

161

Remote address in
request service out
of range

Host

Check parameter in request message

Set Slave Control

The Global Control command initiates a multicast command on the PROFIBUS network to
all configured slaves. This command is always assumed to be successfully executed and no
error will be placed in Cnf.Failure of the response message.

Code

Significance

Error source

Help

0

No error detected

N/A

N/A

Advertising