ILX69-PBM ♦ CompactLogix or MicroLogix Platform

Contents

PROFIBUS Master Communication Module

User Manual

ProSoft Technology, Inc.

Page 53 of 124

February 4, 2015

5.4.2 Studio 5000 Adjustment (Optional)

This (optional) section allows you to tailor the ILX69-PBM input/output sizes to conserve
memory space in the CompactLogix™ processor.

Module Properties

1 With the CompactLogix controller in Offline mode, double-click on the M

ODULE

PBM in

the I/O Configuration dialog to open the Module Properties.

2 In the Module Properties dialog, edit the Connection Parameters I

NPUT

S

IZE

to the sum

of PROFIBUS Input words + 44.

In the example, there are 8 PROFIBUS input bytes, or (4) 16-bit words: 4 + 44 = 48.

For outputs, edit the Connection Parameters O

UTPUT

S

IZE

to the sum of PROFIBUS

Output words + 8.

In the example, there are 8 PROFIBUS output bytes, or (4) 16-bit words: 4 + 8 = 12.

3 Click A

PPLY

, then OK.