ILX69-PBM ♦ CompactLogix or MicroLogix Platform

Contents

PROFIBUS Master Communication Module

User Manual

ProSoft Technology, Inc.

Page 71 of 124

February 4, 2015

GLOBAL-BITS

Bit
Offset

Member
Name

Data
Type

Signification

Meaning if Bit is set

0

Ctrl

BOOL

CONTROL-ERROR

Parameterization error

1

Aclr

BOOL

AUTO-CLEAR-ERROR

Module stopped communication with all
slaves and reached the auto-clear-end
state.

2

Nexc

BOOL

NON-EXCHANGE-ERROR

At least one slave has not reached the
data exchange state and no process data
will be exchanged.

3

Fat

BOOL

FATAL-ERROR

Because of major bus error, no further bus
communication is possible.

4

Eve

BOOL

EVENT-ERROR

The module has detected bus short
circuits. The number of detected events is
contained in the Bus_error_cnt variable.
This bit is set when the first event was
detected and will remain set.

5

NRdy

BOOL

HOST-NOT-READY-
NOTIFICATION

Indicates if the Application program has
set its state to operative or not. If this bit is
set the Application program is not ready to
communicate

6

Tout

BOOL

TIMEOUT-ERROR

The module has detected an overstepped
timeout supervision value because of
rejected PROFIBUS telegrams. It is an
indication for bus short circuits while the
master interrupts the communication. The
number of detected timeouts is available in
the Time_out_cnt variable. This bit will be
set when the first timeout is detected and
will remain set.

7

Reserved1

BOOL

Reserved

Reserved, set to 0

Byte
Offset

Structure
Member

Data
Type

Description

24 to 39 Sl_cfg[16]

SINT(16)

List of Configured Slaves (Bit Field)

40 to 55 Sl_state[16]

SINT(16)

List of Activated Slaves (Bit Field)

56 to 71 Sl_diag[16]

SINT(16)

List of Faulted Slaves (Bit Field)