ProSoft Technology ILX69-PBM User Manual

Page 75

Advertising
background image

ILX69-PBM ♦ CompactLogix or MicroLogix Platform

Contents

PROFIBUS Master Communication Module

User Manual

ProSoft Technology, Inc.

Page 75 of 124

February 4, 2015

Station Status_3
Slave device status information (continued)

Bit
Offset

Member
Name

Data
Type

Description

0 to 6

Reserved0..6

BOOL

Reserved, set to 0

7

ExtDiagOverflow

BOOL

Slave has a large amount of diagnostics data and cannot send it
all at once

DPV1 Alarm Indication

Bytes 80 to 87 contain the DPV1 Alarm Indication registers. These registers provide
incoming alarm indication data required to respond to a DPV1 alarm that originates from a
slave.

Byte
Offset

Member
Name

Data
Type

Description

80

Alarm_Status

SINT

Status of Alarm Pending, see table below

81

AlarmCnt

SINT

Alarm Counter

82

Rem_Add

SINT

Address of slave with Alarm (0 to 126)

83

Slot_Number

SINT

Slot Number (0 to 254)

84

Seq_Nr

SINT

Sequence Number (0 to 31)

85

Alarm_Type

SINT

Alarm Type (1 to 6, 32 to 126)

86

Alarm_Spec

SINT

Alarm Specification (0 to 7)

87

Reserved

SINT

Reserved, set to 0

Alarm_Status

Bit
Offset

Member
Name

Data
Type

Description

0

AlarmInd

BOOL

Alarm Indication

1

Reserved

BOOL

Reserved, set to 0

2

Reserved

BOOL

Reserved, set to 0

3

Reserved

BOOL

Reserved, set to 0

4

Reserved

BOOL

Reserved, set to 0

5

Reserved

BOOL

Reserved, set to 0

6

Reserved

BOOL

Reserved, set to 0

7

AlarmOverrun

BOOL

Alarm Overrun

Advertising