ILX69-PBM ♦ CompactLogix or MicroLogix Platform
User Manual
PROFIBUS Master Communication Module
Page 54 of 124
ProSoft Technology, Inc.
February 4, 2015
Add-On Instruction Definition
1 Double-click on the AOIILX69PBM Add-On-Defined Data Type to open the Add-On
Instruction Definition dialog.
2 Under the Parameters tab, edit the Connection_Input Data Type size to the sum of
PROFIBUS Input words + 44.
In the example, there are 8 PROFIBUS input bytes, or (4) 16-bit words: 4 + 44 = 48.
For outputs, edit the Connection_Output Data Type size to the sum of PROFIBUS
Output words + 8.
In the example, there are 8 PROFIBUS output bytes, or (4) 16-bit words: 4 + 8 = 12.
3 Click A
PPLY
, then OK.