Add-On Instruction Definition

1 Double-click on the AOIILX69PBM Add-On-Defined Data Type to open the Add-On

Instruction Definition dialog.

2 Under the Parameters tab, edit the Connection_Input Data Type size to the sum of

PROFIBUS Input words + 44.

In the example, there are 8 PROFIBUS input bytes, or (4) 16-bit words: 4 + 44 = 48.

For outputs, edit the Connection_Output Data Type size to the sum of PROFIBUS
Output words + 8.

In the example, there are 8 PROFIBUS output bytes, or (4) 16-bit words: 4 + 8 = 12.