ILX69-PBM ♦ CompactLogix or MicroLogix Platform

User Manual

PROFIBUS Master Communication Module

Page 84 of 124

ProSoft Technology, Inc.

February 4, 2015

Name

Data Type

Description

SlaveDeactivated

BOOL

Slave not active

Reserved0...6

BOOL

Reserved

ExtendedDiagnostic
Overflow

BOOL

Slave has a large amount of diagnostics data and cannot send
it all

MasterAddress

SINT

Corresponding master address

IdentNumber

INT

PROFIBUS Identification number

Set Slave Control

This request makes it possible to send commands to one or several slaves. This request
makes it possible to do Sync and Freeze functions. The MSG instruction Request /
Confirmation format is as follows.

ILX69PBM.CONTROL.SlaveControl.SetSlaveControl.

Parameter

Data Type

Value

Description

Initiate

BOOL

0x0000

Triggers the Get Slave Diagnostic command

Address

SINT

0 to 125

Slave address

MSGStatus

-

-

Message Status, see below

SlaveCommand

-

-

Slave Command, see below


MSGStatus - Message Status

Parameter

Data Type

Description

Done

BOOL

Message Status is available

Error

BOOL

Last message was transmitted with an error

DoneCount

DINT

OK response count

ErrorCount

DINT

Error message count


SlaveCommand - Slave Command

Parameter

Data Type

Description

ClearData

BOOL

Clears output data

UnFreeze

BOOL

Unfreezes input data

Freeze

BOOL

Freezes input data

nSync

BOOL

Neutralizes the sync or unsync command

Sync

BOOL

Freezes output data until the sync command is neutralized

GroupSelect

SINT[8]

Group Select, see below.