Adjusting input/output data lengths in the project – ProSoft Technology ILX69-PBM User Manual
Page 51

ILX69-PBM ♦ CompactLogix or MicroLogix Platform
Contents
PROFIBUS Master Communication Module
User Manual
ProSoft Technology, Inc.
Page 51 of 124
February 4, 2015
5.4
Adjusting Input/Output Data Lengths in the Project
If you are using less than 408 bytes of input or 480 bytes of output data, the AOI can be
adjusted to fit the needs of your PROFIBUS network. This section shows you how to
determine the size and parameters to adjust.
5.4.1 Determining the Number of PROFIBUS Inputs/Outputs Used
The ProSoft fdt Configuration Manager shows the total number of inputs and outputs
assigned to all slaves on the PROFIBUS network. This information is used to determine the
adjustment needed in Studio 5000.
1 In the ProSoft fdt Configuration Manager, double-click on the ILX69_PBM icon in the
Network view.