MVI56E-DNPNET ♦ ControlLogix Platform

Contents

DNPNET Ethernet Client/Server Communication Module

User Manual

ProSoft Technology, Inc.

Page 101 of 140

February 13, 2015

The sequence counter field in the returned block is set to the last successfully processed

block 9959 from the ControlLogix processor. Compare this value to that sent by the

ControlLogix processor.
If the values match, the events can be removed from the ControlLogix processor. If the

values do not match, or the ControlLogix processor does not receive a 9959 block, the

ControlLogix processor must re-send the block.

Block 9968: Binary Input Event With CLX Time
Block identification code 9968 sends a set of binary input events with ControlLogix

processor time to the module.

Word Offset
in Block

Data Field(s)

Description

0

Block ID

This field contains the value of 9968 identifying the event block

to the module.

1

Event Count

This field contains the number of events contained in the

block. Valid values for this field are 1 to 30.

2

Sequence

Counter

This field is used to hold the sequence counter for each 9968

block transfer. This is used to synchronize and confirm receipt

of the block by the module.

(Begin Event #1)

3

Point_Number

This is the data point in the DNPNET binary input database

represented by the event.

4

Class_ Override

Bits 0 and 1 are used for class override values of 1, 2, or 3

5

Value

Value of the point, 0 or 1, of bit 0 of this 16-bit word. All other

bits are ignored.

6

Reserved

7 to 10

CLX_Time

64-bit Time as number of microseconds since Jan 1st, 1970

(Next 29 Events)

13 to 22

Ten words of data for Event #2

233 to 242

Ten words of data for Event #30

(End of Event

Data)

243 to 247

Spare

Not used


Up to 30 events can be passed from the ControlLogix processor to the module in each

block. To ensure that the block reached the module and was processed, the module will

send a response read block 9968 to the ControlLogix processor.
The following table describes the format of the block.