ProSoft Technology MVI56E-DNPNET User Manual

Page 79

Advertising
background image

MVI56E-DNPNET ♦ ControlLogix Platform

Contents

DNPNET Ethernet Client/Server Communication Module

User Manual

ProSoft Technology, Inc.

Page 79 of 140

February 13, 2015

Report-by-Exception data is logged to the module’s database

Supports unsolicited messaging

Each DNP3 Ethernet point type is user-configurable in the DNPNET Controller tags of

RSLogix 5000 software

Class assignments are user-definable on a Type and point basis (BI, AI, FI, DI point

types)

Supports clock synchronization from a remote Client or from the processor

Up to 20,000 events are stored for Binary Inputs, Analog Inputs, Floats and Double

Inputs. This varies based on point types in the table above.

Client Specifications
The DNP3 Ethernet port can be configured as a virtual DNP3 Ethernet Client device that

actively issues user-defined DNP3 Ethernet commands to nodes on the network.

The Module supports 300 user defined commands, each one containing its own set of

data link and application layer characteristics

Client logically supports up to 40 server devices

Individual command configuration includes conditional or continuous polling and Poll

Delay Time

Server status and Command status available for transfer to the processor

Event data received from the server devices updates the module database with the

latest data values. Optionally date and time stamped data can be passed to the

processor through a special block 9903 that is enabled/disabled through the parameter

Pass Event Messages to PLC within the configuration of the module. When this option is

used, events from the attached servers are passed to an array in the ladder logic

containing the event data (server device, point index, point value) as well as the time

stamp of the event from the attached server device (value is presented as the 64 bit

UCT time matching the ControlLogix processor date/time format).

Special command handling for Digital Output CROB under processor control for pulse

output control

4.1.3 Hardware Specifications

Specification

Description

Backplane Current Load

800 mA @ 5 Vdc

3 mA @ 24 Vdc

Operating Temperature

0°C to 60°C (32°F to 140°F)

Storage Temperature

-40°C to 85°C (-40°F to 185°F)

Shock

30 g operational

50 g non-operational

Vibration: 5 g from 10 to 150 Hz

Relative Humidity

5% to 95% (without condensation)

LED Indicators

Battery Status (ERR)

Application Status (APP)

Module Status (OK)

4-Character, Scrolling, Alpha-

Numeric LED Display

Shows Module, Version, IP, Port Client/Server

Setting, Port Status, and Error Information

Advertising