OBJECT
REQUEST
RESPONSE
Obj Var Description
Func
Codes
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits)
NOTES
2
16-Bit Frozen Analog
Input
24
3
32-Bit Frozen Analog
Input With Time To
Freeze
88
4
16-Bit Frozen Analog
Input With Time To
Freeze
72
5
32-Bit Frozen Analog
Input Without Flag
32
6
16-Bit Frozen Analog
Input Without Flag
16
32 0
Analog Change Event -
All Variations
1
06, 07,
08
24
Client will generate this
variation
1
32-Bit Analog Change
Event Without Time
1
06, 07,
08
129,
130
17, 28
40
Client will generate and
process this variation.
2
16-Bit Analog Change
Event Without Time
1
06, 07,
08
129,
130
17, 28
24
Client will generate and
process this variation
3
32-Bit Analog Change
Event With Time
1
06, 07,
08
129,
130
17, 28
88
Client will generate and
process this variation.
4
16-Bit Analog Change
Event With Time
1
06, 07,
08
129,
130
17, 28
72
Client will generate and
process this variation
5
Short Floating Point
Analog Change Event
1
06, 07,
08
129,
130
17, 28
40
Client will generate and
process this variation
6
Long Floating Point
Analog Change Event
1
06, 07,
08
129,
130
17, 28
72
Client will generate and
process this variation
33 0
Frozen Analog Event -
All Variations
1
32-Bit Frozen Analog
Event Without Time
40
2
16-Bit Frozen Analog
Event Without Time
24
3
32-Bit Frozen Analog
Event With Time
88
4
16-Bit Frozen Analog
Event With Time
72
40 0
Analog Output Status -
All Variations
1
06
24
Client will generate these
variations and parse the
responses.
1
32-Bit Analog Output
Status
1
06
129,
130
00,01
40
2
16-Bit Analog Output
Status
1
06
129,
130
00, 01
24
3
Single-Precision Float
Analog Output Status 1
06
129,
130
00, 01
40