ProSoft Technology MVI56E-DNPNET User Manual

Page 133

Advertising
background image

MVI56E-DNPNET ♦ ControlLogix Platform

Contents

DNPNET Ethernet Client/Server Communication Module

User Manual

ProSoft Technology, Inc.

Page 133 of 140

February 13, 2015

OBJECT

REQUEST

RESPONSE

Obj Var Description

Func

Codes

Qual
Codes

(hex)

Func

Codes

Qual
Codes

(hex)

Data
Size

(bits)

NOTES

2

16-Bit Frozen Analog

Input

24

3

32-Bit Frozen Analog

Input With Time To

Freeze

88

4

16-Bit Frozen Analog

Input With Time To

Freeze

72

5

32-Bit Frozen Analog

Input Without Flag

32

6

16-Bit Frozen Analog

Input Without Flag

16

32 0

Analog Change Event -

All Variations

1

06, 07,

08

24

Client will generate this

variation

1

32-Bit Analog Change

Event Without Time

1

06, 07,

08

129,

130

17, 28

40

Client will generate and

process this variation.

2

16-Bit Analog Change

Event Without Time

1

06, 07,

08

129,

130

17, 28

24

Client will generate and

process this variation

3

32-Bit Analog Change

Event With Time

1

06, 07,

08

129,

130

17, 28

88

Client will generate and

process this variation.

4

16-Bit Analog Change

Event With Time

1

06, 07,

08

129,

130

17, 28

72

Client will generate and

process this variation

5

Short Floating Point

Analog Change Event

1

06, 07,

08

129,

130

17, 28

40

Client will generate and

process this variation

6

Long Floating Point

Analog Change Event

1

06, 07,

08

129,

130

17, 28

72

Client will generate and

process this variation

33 0

Frozen Analog Event -

All Variations

1

32-Bit Frozen Analog

Event Without Time

40

2

16-Bit Frozen Analog

Event Without Time

24

3

32-Bit Frozen Analog

Event With Time

88

4

16-Bit Frozen Analog

Event With Time

72

40 0

Analog Output Status -

All Variations

1

06

24

Client will generate these

variations and parse the

responses.

1

32-Bit Analog Output

Status

1

06

129,

130

00,01

40

2

16-Bit Analog Output

Status

1

06

129,

130

00, 01

24

3

Single-Precision Float

Analog Output Status 1

06

129,

130

00, 01

40

Advertising