ProSoft Technology MVI56E-DNPNET User Manual
Page 88

Contents
MVI56E-DNPNET ♦ ControlLogix Platform
User Manual
DNPNET Ethernet Client/Server Communication Module
Page 88 of 140
ProSoft Technology, Inc.
February 13, 2015
Word
Offset
Tag Name
Range
Description
40
DNPNET.CONFIG.DNP3
_Server.App_Layer_
Confirm_Tout
1 to 32767
milliseconds
Event data contained in the last response may
be sent again if not confirmed within the
millisecond time period set. If application layer
confirms are used with data link confirms,
ensure that the application layer confirm
timeout is set long enough.
41
DNPNET.CONFIG.DNP3
_Server.Unsolicited_
Response
0 or 1
If set to 0, the server will not send unsolicited
responses. If set to 1, the server will send
unsolicited responses.
42
DNPNET.CONFIG.DNP3
_Server.Class_1_Unsol_
Resp_Min
1 to 255
events
Minimum number of events in Class 1 required
before an unsolicited response will be
generated.
43
DNPNET.CONFIG.DNP3
_Server.Class_2_Unsol_
Resp_Min
1 to 255
events
Minimum number of events in Class 2 required
before an unsolicited response will be
generated.
44
DNPNET.CONFIG.DNP3
_Server.Class_3_Unsol_
Resp_Min
1 to 255
events
Minimum number of events in Class 3 required
before an unsolicited response will be
generated.
45
DNPNET.CONFIG.DNP3
_Server.Unsol_Resp_Del
ay
1 to 32767
milliseconds
Maximum number of 1 millisecond intervals to
wait after an event occurs before sending an
unsolicited response message. If set to 0, only
use minimum number of events.
46
DNPNET.CONFIG.DNP3
_Server.UResp_Client_
Address
0 to 255
retries
DNP destination address where unsolicited
response messages are sent.
47
DNPNET.CONFIG.DNP3
_Server.AI_Events_with_
time
0 or 1
This parameter sets if the analog input events
generated by the module will include the date
and time of the event. If the parameter is set to
0, the default is set to no time data. If the
parameter is set to 1, the default object will
include the time of the event.
48
DNPNET.CONFIG.DNP3
_Server.Events_Require
_
Time_Sync
0 or 1
This parameter is used to determine if events
will be generated by the server module when
its time is not synchronized from a client. If the
parameter is set to 1, no events will be
generated until the module's time has been
synchronized. If the parameter is set to 0,
events will always be generated.
49
DNPNET.CONFIG.DNP3
_Server.Initialize_DNP_
Output_Database
0 or 1
This parameter determines if the module will
request data from the processor to initialize the
DNP database output data areas. If this option
is utilized, ladder logic is required to send the
requested blocks from the processor to the
module.