MVI56E-DNPNET ♦ ControlLogix Platform

User Manual

DNPNET Ethernet Client/Server Communication Module

Page 88 of 140

ProSoft Technology, Inc.

February 13, 2015

Word
Offset

Tag Name

Range

Description

40

DNPNET.CONFIG.DNP3

_Server.App_Layer_

Confirm_Tout

1 to 32767

milliseconds

Event data contained in the last response may

be sent again if not confirmed within the

millisecond time period set. If application layer

confirms are used with data link confirms,

ensure that the application layer confirm

timeout is set long enough.

41

DNPNET.CONFIG.DNP3

_Server.Unsolicited_

Response

0 or 1

If set to 0, the server will not send unsolicited

responses. If set to 1, the server will send

unsolicited responses.

42

DNPNET.CONFIG.DNP3

_Server.Class_1_Unsol_

Resp_Min

1 to 255

events

Minimum number of events in Class 1 required

before an unsolicited response will be

generated.

43

DNPNET.CONFIG.DNP3

_Server.Class_2_Unsol_

Resp_Min

1 to 255

events

Minimum number of events in Class 2 required

before an unsolicited response will be

generated.

44

DNPNET.CONFIG.DNP3

_Server.Class_3_Unsol_

Resp_Min

1 to 255

events

Minimum number of events in Class 3 required

before an unsolicited response will be

generated.

45

DNPNET.CONFIG.DNP3

_Server.Unsol_Resp_Del

ay

1 to 32767

milliseconds

Maximum number of 1 millisecond intervals to

wait after an event occurs before sending an

unsolicited response message. If set to 0, only

use minimum number of events.

46

DNPNET.CONFIG.DNP3

_Server.UResp_Client_

Address

0 to 255

retries

DNP destination address where unsolicited

response messages are sent.

47

DNPNET.CONFIG.DNP3

_Server.AI_Events_with_

time

0 or 1

This parameter sets if the analog input events

generated by the module will include the date

and time of the event. If the parameter is set to

0, the default is set to no time data. If the

parameter is set to 1, the default object will

include the time of the event.

48

DNPNET.CONFIG.DNP3

_Server.Events_Require

_

Time_Sync

0 or 1

This parameter is used to determine if events

will be generated by the server module when

its time is not synchronized from a client. If the

parameter is set to 1, no events will be

generated until the module's time has been

synchronized. If the parameter is set to 0,

events will always be generated.

49

DNPNET.CONFIG.DNP3

_Server.Initialize_DNP_

Output_Database

0 or 1

This parameter determines if the module will

request data from the processor to initialize the

DNP database output data areas. If this option

is utilized, ladder logic is required to send the

requested blocks from the processor to the

module.