4reference – ProSoft Technology MVI56E-DNPNET User Manual

Page 77

Advertising
background image

MVI56E-DNPNET ♦ ControlLogix Platform

Contents

DNPNET Ethernet Client/Server Communication Module

User Manual

ProSoft Technology, Inc.

Page 77 of 140

February 13, 2015

4

Reference

In This Chapter

Product Specifications ...........................................................................77

Functional Overview ..............................................................................80

MVI56E-DNPNET Database Overview ................................................105

MVI56E-DNPNET User Defined Data Types .......................................114

Cable Connections ..............................................................................120

4.1

Product Specifications

The MVI56E-DNPNET (DNP3 Ethernet Client/Server Communication Module) allows

Rockwell Automation ControlLogix I/O compatible processors to interface easily with other

DNP3 Ethernet protocol compatible devices. The module supports DNP3 Ethernet Subset

Level 2 features and some of the Level 3 features.
The module acts as an input/output communications module between the DNP3 Ethernet

network and the ControlLogix backplane. The data transfer from the ControlLogix processor

is asynchronous from the actions on the DNP3 Ethernet network. Databases are user-

defined and stored in the module to hold the data required by the protocol.
This product features:

ProSoft Configuration Builder (PCB): Microsoft Windows

®

-based utility software for

diagnostics. Connect through the module's Ethernet port or use CIPconnect

®

to access

troubleshooting features and functions.

ProSoft Discovery Service (PDS): New Windows-based utility software to find and

display a list of MVI56E modules on the network and to temporarily change a module's

IP address to be able to connect with a module's web page.

CIPconnect-enabled: Allows PC-to-module diagnostics from the Ethernet network

through a ControlLogix

®

1756-ENxT EtherNet/IP™ module.

Personality Card: An industrial-grade compact flash memory card storing the module’s

Ethernet settings, allowing quick and easy replacement.

LED Scrolling Diagnostic Display: 4-character, alphanumeric display, providing

messages for status and alarm data, and for processor and network communication

status.

4.1.1 General Specifications

Single Slot - 1756 ControlLogix

®

backplane compatible

10/100 MB Ethernet port for network configuration and diagnostics with Auto Cable

Crossover Detection

Add-On Instruction (AOI) used for data transfers between module and processor and for

module configuration

Advertising