6 dnpnet.config.dnp_server_override – ProSoft Technology MVI56E-DNPNET User Manual

Page 36

Advertising
background image

Contents

MVI56E-DNPNET ♦ ControlLogix Platform

User Manual

DNPNET Ethernet Client/Server Communication Module

Page 36 of 140

ProSoft Technology, Inc.

February 13, 2015

Tag Name

Range

Description

DNPNET.CONFIG.DNP3_Clie

nt.Only_Time_Sync_Servers_I

f_Synced

0 or 1

This parameter determines if the client will

send a time sync message to servers when its

own time has not yet been synced via PLC or

a connected client. If set to 0, the client will

send a time sync to connected servers even if

its own clock has not been synced by the PLC

or another connected client. If set to 1, the

client will not send time syncs to servers until it

has been synced by the PLC or a connected

client.

DNPNET.CONFIG.DNP3_Clie

nt.Use_Binary_Output_status_

Data

0 or 1

Enable database and functions for reading the

status of Binary Outputs (object 10).

DNPNET.CONFIG.DNP3_Clie

nt.Use_Analog_Output_status

_Data

0 or 1

Enable database and functions for reading the

status of Analog Outputs (object 40).

DNPNET.CONFIG.DNP3_Clie

nt.Dont_Process_IIN

0 or 1

By default (0), the Client module will

automatically make requests to servers that

have IIN bits set for class data, need time,

restart, or buffer overflow until these IIN bits

have been cleared. If this parameter is set to

1, the Client will NOT automatically make

these requests as a result of these IIN bits

being set.

DNPNET.CONFIG.DNP3_Clie

nt.reserved_0

-

-

2.3.6 DNPNET.CONFIG.DNP_Server_Override

Assigns Class and Deadband overrides to individual point types. You can adjust the size of

each of the 5 point type arrays.

Tag Name

Range

Description

DNPNET.CONFIG.DNP_Serv

er_Override.Binary_Inputs.

n/a

Number of binary input words contained in the

IED database to be transferred to the PLC and

obtained from the attached IED units.

This array size ranges from 0 to 1000.

Point_Number

0 to Number of

points configured

Point number

index to be

overridden

Point number index to be overridden

Class

1 to 3

Class number assigned to point number

specified above

DNPNET.CONFIG.DNP_Serv

er_Override.Analog16_Inputs.

n/a

Number of 16-bit analog input points contained

in the IED database to be transferred to the

PLC and obtained from the attached IED units.

This array size ranges from 0 to 1000.

Point_Number

0 to Number of

points configured

Point number index to be overridden