OBJECT

REQUEST

RESPONSE

Obj Var Description

Func

Codes

Qual
Codes

(hex)

Func

Codes

Qual
Codes

(hex)

Data
Size

(bits)

NOTES

6

Long Floating Point

Analog Change

Event

1

06, 07,

08

129, 130 17, 28

72

Server will return this

variation

7

Short Floating Point

Analog Change

Event With Time

1

06, 07,

08

129, 130 17, 28

88

Server will return this

variation

8

Long Floating Point

Analog Change

Event With Time

1

06, 07,

08

129, 130 17, 28

120

Server will return this

variation

33 0

Frozen Analog Event

- All Variations

Server will return Unknown

Object to this request

1

32-Bit Frozen Analog

Event Without Time

40

Server will return Unknown

Object to this request

2

16-Bit Frozen Analog

Event Without Time

24

Server will return Unknown

Object to this request

3

32-Bit Frozen Analog

Event With Time

88

Server will return Unknown

Object to this request

4

16-Bit Frozen Analog

Event With Time

72

Server will return Unknown

Object to this request

5

Short Floating Point

Frozen Analog Event

40

Server will return Unknown

Object to this request

6

Long Floating Point

Frozen Analog Event

72

Server will return Unknown

Object to this request

7

Short Floating Point

Frozen Analog Event

With Time

88

Server will return Unknown

Object to this request

8

Long Floating Point

Frozen Analog Event

With Time

120

Server will return Unknown

Object to this request

40 0

Analog Output Status

- All Variations

1

06

24

Server will return variation 2

data

1

32-Bit Analog Output

Status

1

06

129, 130 00, 01

40

Server will return this

variation

2

16-Bit Analog Output

Status

1

06

129, 130 00, 01

24

Server will return this

variation

3

Short Floating Point

Analog Output Status

1

06

129, 130 00, 01

40

Server will return this

variation

4

Long Floating Point

Analog Output Status

1

06

129, 130 00, 01

72

Server will return this

variation

41 0

Analog Output Block

- All Variations

24

Server will respond to this

request using variation 2 data

1

32-Bit Analog Output

Block

3, 4, 5,

6

17, 28

129, 130 00, 01

40

Server will respond to this

request

2

16-Bit Analog Output

Block

3, 4, 5,

6

17, 28

129

Echo of

Request

24