ProSoft Technology MVI56E-DNPNET User Manual

Page 132

Advertising
background image

Contents

MVI56E-DNPNET ♦ ControlLogix Platform

User Manual

DNPNET Ethernet Client/Server Communication Module

Page 132 of 140

ProSoft Technology, Inc.

February 13, 2015

OBJECT

REQUEST

RESPONSE

Obj Var Description

Func

Codes

Qual
Codes

(hex)

Func

Codes

Qual
Codes

(hex)

Data
Size

(bits)

NOTES

7

32-Bit Delta Counter

Change Event With

Time

88

8

16-Bit Delta Counter

Change Event With

Time

72

23 0

Frozen Counter Event -

All Variations

1

32-Bit Frozen Counter

Event Without Time

40

2

16-Bit Frozen Counter

Event Without Time

24

3

32-Bit Frozen Delta

Counter Event Without

Time

40

4

16-Bit Frozen Delta

Counter Event Without

Time

24

5

32-Bit Frozen Counter

Event With Time

88

6

16-Bit Frozen Counter

Event With Time

72

7

32-Bit Frozen Delta

Counter Event With

Time

88

8

16-Bit Frozen Delta

Counter Event With

Time

72

30 0

Analog Input - All

Variations

1

06

16

Client will generate this

variation

1

32-Bit Analog Input

1

06

129,

130

00, 01

40

Client will generate and

process this variation

2

16-Bit Analog Input

1

06

129,

130

00, 01

24

Client will generate and

process this variation

3

32-Bit Analog Input

Without Flag

1

06

129,

130

00, 01

32

Client will not generate and

will not process this variation

4

16-Bit Analog Input

Without Flag

1

06

129,

130

00, 01

16

Client will generate and

process this variation

5

Short Floating Point

Analog Input

1

06

129,

130

00, 01

40

Client will generate and

process this variation

6

Long Floating Point

Analog Input

1

06

129,

130

00, 01

72

Client will generate and

process this variation

31 0

Frozen Analog Input -

All Variations

1

32-Bit Frozen Analog

Input

40

Advertising