ProSoft Technology MVI56E-DNPNET User Manual

Page 32

Advertising
background image

Contents

MVI56E-DNPNET ♦ ControlLogix Platform

User Manual

DNPNET Ethernet Client/Server Communication Module

Page 32 of 140

ProSoft Technology, Inc.

February 13, 2015

Tag Name

Range

Description

DNPNET.CONFIG.DNP3_Ser

ver.Analog16_Input_Class

0 to 3

This parameter specifies the default class to

be utilized for all the 16-bit analog input points

in the DNP database that are not defined in

the override list section.

DNPNET.CONFIG.DNP3_Ser

ver.Analog32_Input_Class

0 to 3

This parameter specifies the default class to

be utilized for all the 32-bit analog input points

in the DNP database that are not defined in

the override list section.

DNPNET.CONFIG.DNP3_Ser

ver.Float_Class

0 to 3

This parameter specifies the default class to

be utilized for all the float input points in the

DNP database that are not defined in the

override list section.

DNPNET.CONFIG.DNP3_Ser

ver.Double_Class

0 to 3

This parameter specifies the default class to

be utilized for all the double input points in the

DNP database that are not defined in the

override list section.

DNPNET.CONFIG.DNP3_Ser

ver.Analog16_Input_Deadban

d

0 to 32767

This parameter specifies the default deadband

value assigned to all points not defined in the

override list for the 16-bit analog input point

type in the DNP database.

DNPNET.CONFIG.DNP3_Ser

ver.Analog32_Input_Deadban

d

0 to

2,147,483,647

This parameter specifies the default deadband

value assigned to all points not defined in the

override list for the 32-bit analog input point

type in the DNP database.

DNPNET.CONFIG.DNP3_Ser

ver.Float_Deadband

0 to maximum

float value

This parameter specifies the default deadband

value assigned to all points not defined in the

override list for the float input point type in the

DNP database.

DNPNET.CONFIG.DNP3_Ser

ver.Double_Deadband

0 to maximum

double value

This parameter specifies the default deadband

value assigned to all points not defined in the

override list for the double input point type in

the DNP database.

DNPNET.CONFIG.DNP3_Ser

ver.SelectOperate_Arm_Time

1 to 32767

Time period after select command received in

which operate command will be performed.

After the select command is received, the

operate command will only be honored if it

arrives within this period of time.

DNPNET.CONFIG.DNP3_Ser

ver.Write_Time_Interval

0 to 1440

minutes

Time interval to set the need time IIN bit

(0=never), which will cause the client to write

the time. Stored in milliseconds in the module

memory.

DNPNET.CONFIG.DNP3_Ser

ver.Spare1_Always_0

0,1, or 2 (Coded

Value)

IED can request acknowledgement from client

station when sending data. The codes are as

follows: 0=Never, 1=Sometimes, 2=Always

DNPNET.CONFIG.DNP3_Ser

ver. Spare1_Always_1

1 to 32767

milliseconds

Time period to wait for client Data Link

confirmation of last frame sent. This time is in

milliseconds. This parameter is only used if the

frame is sent with confirmation requested.

Advertising