ProSoft Technology MVI56E-DNPNET User Manual

Page 126

Advertising
background image

Contents

MVI56E-DNPNET ♦ ControlLogix Platform

User Manual

DNPNET Ethernet Client/Server Communication Module

Page 126 of 140

ProSoft Technology, Inc.

February 13, 2015

OBJECT

REQUEST

RESPONSE

Obj Var Description

Func

Codes

Qual
Codes

(hex)

Func

Codes

Qual
Codes

(hex)

Data
Size

(bits)

NOTES

3

32-Bit Analog Input

Without Flag

1

06

129, 130 00, 01

32

Server will return this

variation

4

16-Bit Analog Input

Without Flag

1

06

129, 130 00, 01

16

Server will return this

variation

5

Short Floating Point

Analog Input

1

06

129, 130 00, 01

40

Server will return this

variation

6

Long Floating Point

Analog Input

1

06

129, 130 00, 01

72

Server will return this

variation

31 0

Frozen Analog Input -

All Variations

Server will return Unknown

Object to this request

1

32-Bit Frozen Analog

Input

40

Server will return Unknown

Object to this request

2

16-Bit Frozen Analog

Input

24

Server will return Unknown

Object to this request

3

32-Bit Frozen Analog

Input With Time To

Freeze

88

Server will return Unknown

Object to this request

4

16-Bit Frozen Analog

Input With Time To

Freeze

72

Server will return Unknown

Object to this request

5

32-Bit Frozen Analog

Input Without Flag

32

Server will return Unknown

Object to this request

6

16-Bit Frozen Analog

Input Without Flag

16

Server will return Unknown

Object to this request

7

Short Floating Point

Frozen Analog Input

40

Server will return Unknown

Object to this request

8

Long Floating Point

Frozen Analog Input

72

Server will return Unknown

Object to this request

32 0

Analog Change

Event - All Variations

1

06, 07,

08

24

Server will return variation 2

data

1

32-Bit Analog

Change Event

Without Time

1

06, 07,

08

129, 130 17, 28

40

Server will return this

variation

2

16-Bit Analog

Change Event

Without Time

1

06, 07,

08

129, 130 17, 28

24

Server will return this

variation

3

32-Bit Analog

Change Event With

Time

1

06, 07,

08

129, 130 17, 28

88

Server will return this

variation

4

16-Bit Analog

Change Event With

Time

1

06, 07,

08

129, 130 17, 28

72

Server will return this

variation

5

Short Floating Point

Analog Change

Event

1

06, 07,

08

129, 130 17, 28

40

Server will return this

variation