Error Code

Name

Description

104

Too many analog output points Too many analog output points are configured for

the module. Maximum value is 960.

105

Too many binary input events Too many binary input events are configured for

the module. Maximum value is 400.

106

Too many analog input events Too many analog input events are configured for

the module. Maximum value is 400.

107

Invalid analog input deadband Deadband value for analog input events is out of

range. Value must be in the range of 0 to 32767.

108

Not enough memory

There is not enough memory in the module to

configure the module as specified.

109

Invalid block transfer delay for

error/status blocks

Block transfer delay value specified is too low.

110

File count invalid

The file count must be in the range of 0 to 6.

111

Invalid file record size

The file record size must be in the range of 1 to

120.

112

Invalid block identification code

for file

The file block transfer code must be in the range

of 100 to 120.


3.7.4 Port Configuration Errors

Error
Code

Name

Description

212

Invalid DNP address

The DNP address specified in the

configuration is not valid (0 to 65534).

213

Invalid DNP port baud rate

The baud rate code specified in the

configuration is not valid.

219

Invalid DNP data link layer confirm

mode

The data link confirmation mode code is not

valid in the configuration.

220

Invalid DNP data link confirm time-out The data link time-out period specified in the

configuration is 0. It must be an integer in the

range of 1 to 65535.

222

Invalid DNP select/operate arm time

duration

The select/operate arm timer is set to 0. It

must be an integer in the range of 1 to 65535.

223

Invalid DNP application layer confirm

time-out

The application layer confirm time-out value is

set to 0. It must be an integer in the range of 1

to 65535.

224

Invalid DNP write time interval

The write time interval is not in the data range

in the configuration. The value must be in the

range of 0 to 1440.

225

Invalid DNP unsolicited response

mode

The unsolicited response mode code is not

valid in the configuration.

226

Invalid DNP unsolicited response

minimum quantity for Class 1

The unsolicited response minimum quantity for

Class 1 is not valid in the configuration. Value

must be an integer in the range of 1 to 255.