ProSoft Technology MVI56E-DNPNET User Manual

Page 95

Advertising
background image

MVI56E-DNPNET ♦ ControlLogix Platform

Contents

DNPNET Ethernet Client/Server Communication Module

User Manual

ProSoft Technology, Inc.

Page 95 of 140

February 13, 2015

Word Offset
Start

Stop

Data Field(s)

Description

123

128

CROB 21

CROB block data as defined below

129

134

CROB 22

CROB block data as defined below

135

140

CROB 23

CROB block data as defined below

141

146

CROB 24

CROB block data as defined below

147

152

CROB 25

CROB block data as defined below

153

158

CROB 26

CROB block data as defined below

159

164

CROB 27

CROB block data as defined below

165

170

CROB 28

CROB block data as defined below

171

176

CROB 29

CROB block data as defined below

177

182

CROB 30

CROB block data as defined below

183

188

CROB 31

CROB block data as defined below

189

194

CROB 32

CROB block data as defined below

195

200

CROB 33

CROB block data as defined below

201

206

CROB 34

CROB block data as defined below

207

212

CROB 35

CROB block data as defined below

213

218

CROB 36

CROB block data as defined below

219

224

CROB 37

CROB block data as defined below

225

230

CROB 38

CROB block data as defined below

231

236

CROB 39

CROB block data as defined below

237

242

CROB 40

CROB block data as defined below

243

248

Spare

Not Used

249

249

Block ID

This field contains the block identification code of 9910 for

the block.


The format of each 6 word data region in the block is as follows:

Word Offset

Definitions

Description

0

Point Number

This field contains the BO point number for the following

CROB command.

1

Control Code

Byte value Control Code of the CROB message received.

Control code 81 = trip, 41 = close, and 1 = pulse.

Count

Byte value of number of pulses

2 to 3

On Time

This double-word contains the ‘on’ time interval for the CROB

block.

4 to 5

Off Time

This double-word contains the ‘off’ time interval for the CROB

block.

Block 9949: Request Server Communication Error Table
If the ControlLogix processor sends a block 9949, the <Model Number> module responds

with a server communication error listing.