ProSoft Technology MVI56E-DNPNET User Manual

Page 97

Advertising
background image

MVI56E-DNPNET ♦ ControlLogix Platform

Contents

DNPNET Ethernet Client/Server Communication Module

User Manual

ProSoft Technology, Inc.

Page 97 of 140

February 13, 2015

Bad CRC

This value represents the number of bad CRC values received from the

server device.

Buff Overflow

This value represents the number of buffer overflow messages received

from the server device.

Transaction

Sequence Number

This value represents the number of incorrect transport layer sequence

number errors.

Confirm Retries

This value represents the number of data link layer confirm request retries.

Confirm Failures

This value represents the number of data link layer confirm request

failures.

No Application Layer

Responses

This value represents the number of application layer no responses to

requests.

Block 9950: Read Command Error List
If the ControlLogix processor sends a block number of 9950 to the module, the application

will respond with an MVI56E-DNPNET Client command error list. Each command in the

system has a data word set aside for its last error code. This value is set by the DNPNET

Client command list task and the values correspond to the errors listed in the error section of

this documentation. This can be accessed 200 commands at a time.
Block format of Command Error List Request sent to the module from the ControlLogix

processor.

Word Offset
in Block

Data Field(s)

Description

0

Block ID

This field contains the value of 9950 identifying the block type

to the module.

1

Number of

Commands to

report

This field contains the number of commands to report in the

response message. The value has a range of 1 to 200.

2

Start Index of First

Command

This parameter sets the index in the command list where to

start. The first command in the list has a value of 0. The last

index in the list has a value of (MaxCommands -1).

3 to 247

Spare

Not Used


Block format of Command Error List Response sent to the ControlLogix processor from

module

Word Offset
in Block

Data Field(s)

Description

0

Reserved

Reserved

1

Block ID

This is the next block requested by the module.

2

Number of

Commands

reported

This field contains the number of commands contained in the

block that must be processed by the PLC. This field will have a

value of 1 to 200.