MVI56E-DNPNET ♦ ControlLogix Platform

Contents

DNPNET Ethernet Client/Server Communication Module

User Manual

ProSoft Technology, Inc.

Page 81 of 140

February 13, 2015

Main Logic Loop
Upon completing the power up configuration process, the module enters an infinite loop

performing the following functions:

Backplane Data Transfer
The MVI56E-DNPNET module communicates directly over the ControlLogix backplane.

Data is paged between the module and the ControlLogix processor across the backplane

using the module's input and output images. The update frequency of the images is

determined by the scheduled scan rate defined by the user for the module and the

communication load on the module. Typical updates are in the range of 1 to 10 milliseconds

per block of information.
This bi-directional transference of data is accomplished by the module filling in data in the

module's input image to send to the processor. Data in the input image is placed in the

Controller Tags in the processor by the ladder logic. The input image for the module is set to

250 words. This large data area permits fast throughput of data between the module and the

processor.
The processor inserts data to the module's output image to transfer to the module. The

module's program extracts the data and places it in the module's internal database. The

output image for the module is set to 248 words. This large data area permits fast

throughput of data from the processor to the module.