Error
Code

Name

Description

227

Invalid DNP unsolicited response

minimum quantity for Class 2

The unsolicited response minimum quantity for

Class 2 is not valid in the configuration. Value

must be an integer in the range of 1 to 255.

228

Invalid DNP unsolicited response

minimum quantity for Class 3

The unsolicited response minimum quantity for

Class 3 is not valid in the configuration. Value

must be an integer in the range of 1 to 255.

230

Invalid DNP unsolicited response

destination address

The unsolicited response destination address

is not valid in the configuration. Value must be

in the range of 1 to 65534.

3.7.5 Application Layer Errors

Error Code

Name

Description

1000

Device index invalid

The device index in the request or response

message is not found in the slave list.

1001

Duplicate request in application

layer queue

The newly submitted message to the application

layer already exists in the queue. The message is

ignored.

1002

COM port device removed from

system

The communication port for the message has

been uninstalled on the system. This error should

never occur as the communication ports are only

uninstalled when the module's program is

terminated.

1003

Sequence number error

The application sequence number in the response

message does not match that based on the last

request message. This indicates application layer

messages are received out of order.

1004

Response to select before

operate does not match

The select response message received from the

slave module is not that expected from the last

select request. This indicates a synchronization

problem between the Master and slave devices.

1005

Response does not contain

date/time object

The response message from the slave device

does not contain a date/time object. The Master

expects this object for the response message.

1006

Time-out condition on

response

The slave device did not respond to the last

request message from the Master within the time-

out set for the IED device. The application layer

time-out value is specified for each IED unit in the

slave configuration table in the module. This table

is established each time the module performs the

restart operation.

1007

Function code in application

layer message not supported

The function code returned in the response

message is not valid for the application layer or

not supported by the module.

1008

Read operation not supported

for object/variation

The application layer response message contains

an object that does not support the read function.

Advertising