ProSoft Technology MVI56E-DNPNET User Manual
Page 54

Contents
MVI56E-DNPNET ♦ ControlLogix Platform
User Manual
DNPNET Ethernet Client/Server Communication Module
Page 54 of 140
ProSoft Technology, Inc.
February 13, 2015
1
Configure the path between the 1756-ENBT connected to your PC and the MVI56E-
DNPNET module.
o
If the module is located in a remote rack, add more racks to configure the full path.
o
The path can only contain ControlNet or Ethernet/IP networks.
o
The maximum number of supported racks is six.
2
Click C
ONSTRUCT
CIP
P
ATH
to build the path in text format
3
Click OK
to confirm the configured path.
The following examples should provide a better understanding on how to set up the path for
your network.
Example 1: Local Rack Application
For this example, the MVI56E-DNPNET module is located in the same rack as the 1756-
ENBT that is connected to the PC.
Ethernet
Rack 1
MVI56E Module
1756-ENBT
0 1 2 3
Rack 1
Slot
Module
Network Address
0
ControlLogix Processor
-
1
Any
-
2
MVI56E-DNPNET
-
3
1756-ENBT
IP=192.168.0.100
1
In the tree view in ProSoft Configuration Builder, right-click the MVI56E-DNPNET icon to
open a shortcut menu.