MVI56E-DNPNET ♦ ControlLogix Platform

User Manual

DNPNET Ethernet Client/Server Communication Module

Page 54 of 140

ProSoft Technology, Inc.

February 13, 2015

1

Configure the path between the 1756-ENBT connected to your PC and the MVI56E-

DNPNET module.

o

If the module is located in a remote rack, add more racks to configure the full path.

o

The path can only contain ControlNet or Ethernet/IP networks.

o

The maximum number of supported racks is six.

2

Click C

ONSTRUCT

CIP

P

ATH

to build the path in text format

3

Click OK

to confirm the configured path.

The following examples should provide a better understanding on how to set up the path for

your network.

Example 1: Local Rack Application
For this example, the MVI56E-DNPNET module is located in the same rack as the 1756-

ENBT that is connected to the PC.

Ethernet

Rack 1

MVI56E Module

1756-ENBT

0 1 2 3

Rack 1

Slot

Module

Network Address

0

ControlLogix Processor

-

1

Any

-

2

MVI56E-DNPNET

-

3

1756-ENBT

IP=192.168.0.100


1

In the tree view in ProSoft Configuration Builder, right-click the MVI56E-DNPNET icon to

open a shortcut menu.