3diagnostics and troubleshooting – ProSoft Technology MVI56E-DNPNET User Manual

Page 45

Advertising
background image

MVI56E-DNPNET ♦ ControlLogix Platform

Contents

DNPNET Ethernet Client/Server Communication Module

User Manual

ProSoft Technology, Inc.

Page 45 of 140

February 13, 2015

3

Diagnostics and Troubleshooting

In This Chapter

Ethernet LED Indicators .........................................................................45

Clearing a Fault Condition .....................................................................47

Troubleshooting .....................................................................................47

Setting Up ProSoft Configuration Builder ...............................................48

Connecting Your PC to the Module .......................................................51

Using the Diagnostics Menu in ProSoft Configuration Builder ...............62

Communication Error Codes ..................................................................70

Connect to the Module’s Web Page ......................................................74

The module provides information on diagnostics and troubleshooting in the following forms:

LED status indicators on the front of the module provide information on the module’s

status.

Status data contained in the module can be viewed in ProSoft Configuration Builder

through the Ethernet port.

Status data values are transferred from the module to the processor.

3.1

Ethernet LED Indicators

The Ethernet LEDs indicate the module's Ethernet port status as follows:

LED

State

Description

Data

OFF

Ethernet connected at 10Mbps duplex speed

AMBER Solid Ethernet connected at 100Mbps duplex speed

Link

OFF

No physical network connection is detected. No Ethernet

communication is possible. Check wiring and cables.

GREEN Solid

or Blinking

Physical network connection detected. This LED must be ON solid

for Ethernet communication to be possible.

3.1.1 Scrolling LED Status Indicators

The scrolling LED display indicates the module’s operating status as follows:

Initialization Messages

Code

Message

Boot / DDOK

Module is initializing

Advertising