Communication error codes – ProSoft Technology MVI56E-DNPNET User Manual

Page 70

Advertising
background image

Contents

MVI56E-DNPNET ♦ ControlLogix Platform

User Manual

DNPNET Ethernet Client/Server Communication Module

Page 70 of 140

ProSoft Technology, Inc.

February 13, 2015

3.7

Communication Error Codes

3.7.1 General Command Errors

Error
Code

Name

Description

1

Device not defined

The IED slave address referenced in the

command is not defined in the module. Check

to make sure there is an entry in the slave

table for each slave device referenced in the

command list.

2

Invalid command

This command is not valid. Check to make

sure the slave address parameter is greater

than or equal to zero and that the point count

is not set to zero.

3

Object not supported

The data object in the command is not

supported by the module. Refer to the DNP

subset for the Master Port.

4

Command function not supported

The function specified in the command is not

supported for the object type selected. Refer to

the DNP subset for the Master Port.

5

Command variation not supported

The variation specified in the command is not

supported for the object type selected.

6

Object 10 not enabled

The command is not supported unless Binary

Output Status is enabled

7

Object 40 not enabled

The command is not supported unless Analog

Output Status is enabled

8

Invalid time/date poll command

This time/date object poll command is not

valid.

9

Time/date poll command cannot

execute

This time/date object poll command cannot

execute because the module's clock has not

been synced from a valid source (from PLC or

connected Client)