background image

4 - 31

4. OPERATION


4.4.4 Data setting type home position return

Data setting type home position return is used when it is desired to determine any position as a home
position. JOG operation, manual pulse generator operation or like can be used for movement.

(1) Signals, parameters

Set the input signals and parameters as follows.

Item Device/Parameter

used Description

Automatic/manual selection (MD0) Short MD0-SG (ON).
Point table No. selection 1 (DI0)

Open DI0-SG (OFF).

Manual home position return mode
selection

Point table No. selection 2 (DI1)

Open DI1-SG (OFF).

Data setting type home position return

Parameter No.8

2 : Data setting type home position

return is selected.

Home position return position data

Parameter No.42

Use to set the current position on completion
of home position return.


(2) Timing chart

Movement finish (MEND)

Rough match

(CPO)

Home position

return completion

(ZP)

Servo motor speed

Forward rotation

start (ST1)

ON
OFF
ON
OFF
ON
OFF

ON
OFF

3ms or less

Home position address
Parameter No. 42

ON
OFF

Automatic/manual selection

(MD0)

5ms or more

Movement to the home position

Operation for home position return

ON
OFF

Reverse rotation

start (ST2)

The parameter No.42 (home position return position data) setting value is the positioning address
after the home position return is completed.