Parameters – MITSUBISHI ELECTRIC MR-J2S- CP User Manual

Page 150

Advertising
background image

5 - 13

5. PARAMETERS

Class No. Symbol

Name and Function

Initial
value

Unit

Setting

range

46
47

*LMP Software

limit

Used to set the address increment side software stroke limit. The software limit
is made invalid if this value is the same as in "software limit ".
(Refer to section 5.2.8)
Set the same sign to parameters No.46 and 47. Setting of different signs will
result in a parameter error.

Set address:

Upper 3
digits

Lower 3
digits

Parameter No. 47
Parameter No. 46

0

10

STM

m

999999

to

999999

48
49

*LMN Software limit

Used to set the address decrement side software stroke limit. The software limit
is made invalid if this value is the same as in "software limit ".
(Refer to section 5.2.8)
Set the same sign to parameters No.48 and 49. Setting of different signs will
result in a parameter error.

Set address:

Upper 3
digits

Lower 3
digits

Parameter No. 49
Parameter No. 48

0

10

STM

m

999999

to

999999

50
51

*LPP Position range output address

Used to set the address increment side position range output address. Set the
same sign to parameters No.50 and 51. Setting of different signs will result in a
parameter error.
In parameters No. 50 to 53, set the range where position range (POT) turns on.

Set address:

Upper 3
digits

Lower 3
digits

Parameter No. 51
Parameter No. 50

0

10

STM

m

999999

to

999999

E

xpa

n

si

on

pa

ra

m

et

ers

1

52
53

*LNP Position range output address

Used to set the address decrement side position range output address. Set the
same sign to parameters No.52 and 53. Setting of different signs will result in a
parameter error.

Set address:

Upper 3
digits

Lower 3
digits

Parameter No. 53
Parameter No. 52

0

10

STM

m

999999

to

999999