13 - 7

13. CHARACTERISTICS


13.5 Inrush currents at power-on of main circuit and control circuit

The following table indicates the inrush currents (reference value) that will flow when the maximum
permissible voltage (253VAC) is applied at the power supply capacity of 2500kVA and the wiring length of
1m.

Inrush Currents (A

0-p

)

Servo Amplifier

Main circuit power supply (L

1

, L

2

, L

3

)

Control circuit power supply (L

11

, L

21

)

MR-J2S-10CP 20CP

30A (Attenuated to approx. 5A in 10ms)

MR-J2S-40CP 60CP

30A (Attenuated to approx. 5A in 10ms)

MR-J2S-70CP 100CP

54A (Attenuated to approx. 12A in 10ms)

70 to 100A

(Attenuated to approx. 0A in 0.5 to 1ms)

MR-J2S-200CP 350CP

120A (Attenuated to approx. 12A in 20ms)

100 to 130A

(Attenuated to approx. 0A in 0.5 to 1ms)

MR-J2S-500CP

44A (Attenuated to approx. 20A in 20ms)

MR-J2S-700CP

88A (Attenuated to approx. 20A in 20ms)

30A

(Attenuated to approx. 0A in several ms)

MR-J2S-10CP1 20CP1

59A (Attenuated to approx. 5A in 4ms)

MR-J2S-40CP1

72A (Attenuated to approx. 5A in 4ms)

100 to 130A

(Attenuated to approx. 0A in 0.5 to 1ms)


Since large inrush currents flow in the power supplies, always use no-fuse breakers and magnetic
contactors. (Refer to section 14.2.2.)
When circuit protectors are used, it is recommended to use the inertia delay type that will not be tripped
by an inrush current.