3 - 34

3. SIGNALS AND WIRING


(3) Timing charts

(a) Servo-on (SON) command (from controller) ON/OFF

Tb (ms) after servo-on (SON) is switched off, servo lock is released and the servo motor coasts.
If the electromagnetic brake is made valid in the servo lock status, the brake life may be shorter.
For use in vertical lift and similar applications, therefore, set delay time (Tb) to the time which is
about equal to the electromagnetic brake operation delay time and during which the load will not
drop.

(60ms)

(80ms)

Electromagnetic

brake interlock

(MBR)

(Note 1)

ON

OFF

0 r/min

Base circuit

Servo motor speed

Servo-on(RYn0)

ON

OFF

Coasting

Tb

Electromagnetic

brake operation

delay time

ON

OFF

Release

Activate

Forward rotation start

(ST1) or reverse rotation

start (ST2)

Electromagnetic

brake

Release delay time and external relay (Note 2)

(Note 3)

ON

OFF

Note 1. ON: Electromagnetic brake is not activated.

OFF: Electromagnetic brake is activated.

2. Electromagnetic brake is released after delaying for the release delay time of electromagnetic brake and operation time of

external circuit relay. For the release delay time of electromagnetic brake, refer to the Servo Motor Instruction Manual.

3. After the electromagnetic brake is released, turn ON the ST1 or ST2.

(b) Forced stop (EMG) ON/OFF

Electromagnetic brake release

Electromagnetic brake

Dynamic brake

Electromagnetic brake

Dynamic brake

(ON)

Forward
rotation

Electromagnetic
brake interlock (MBR)

Servo motor speed

Base circuit

Forced stop (EMG)

ON

OFF

ON

OFF

(Note)

0r/min

Invalid

Valid (OFF)

Electromagnetic brake

operation delay time

(180ms)

(180ms)

(10ms)

Note. ON: Electromagnetic brake is not activated.

OFF: Electromagnetic brake is activated.