background image

4 - 4

4. OPERATION

(f) Home position return

Perform home position return as required. Refer to section 4.4 for home position return types. A
parameter setting example for dog type home position return is given here.

Parameter Name Setting

Description

No.8

Home position return type

000

Dog type home position return is selected.
Home position return is started in address
incremented direction.
Proximity dog (DOG) is valid when DOG-
SG are opened.

No.9

Home position return speed

1000

Motion is made up to proximity dog at 1000r/min.

No.10

Creep speed

10

Motion is made up to home position at 10r/min.

No.11

Home position shift distance

0

No home position shift

No.42

Home position return position data

Use to set the current position on completion of home
position return.

No.43

Moving distance after proximity dog

Not used in dog type home position return.

After setting the above parameters, switch power off once. Then switch power on again to make the
set parameter values valid.
Set the input signals as listed below and switch on the forward rotation start (ST1) to execute
home position return.

Device name

Symbol

ON/OFF

Description

Automatic/manual selection

MD0

ON

Point table No. selection 1

DI0

OFF

Point table No. selection 2

DI1

OFF

Home position return mode is selected.

Forward rotation stroke end

LSP

ON

CCW rotation side limit switch is turned on.

Reverse rotation stroke end

LSN

ON

CW rotation side limit switch is turned on.

Servo-on

SON

ON

Servo is switched on.

(g) Automatic operation

Set the input signals as listed below and switch on the forward rotation start (ST1) to execute
automatic operation in accordance with point table No.1.

Device name

Symbol

ON/OFF

Description

Automatic/manual selection

MD0

ON

Automatic operation mode is selected.

Servo-on

SON

ON

Servo is switched on.

Forward rotation stroke end

LSP

ON

CCW rotation side limit switch is turned on.

Reverse rotation stroke end

LSN

ON

CW rotation side limit switch is turned on.

Point table No. selection 1

DI0

ON

Point table No. selection 2

DI1

OFF

Point table No.1 is selected.

(h) Stop

In any of the following statuses, the servo amplifier interrupts and stops the operation of the servo
motor.
When the servo motor used is equipped with an electromagnetic brake, refer to section 3.9 (3). Note
that forward rotation stroke end (LSP), reverse rotation stroke end (LSN) off has the same
stopping pattern as described below.
1) Servo-on (SON) OFF

The base circuit is shut off and the servo motor coasts.

2) Alarm occurrence

When an alarm occurs, the base circuit is shut off and the dynamic brake is operated to bring the
servo motor to a sudden stop.

3) Forced stop (EMG) OFF

The base circuit is shut off and the dynamic brake is operated to bring the servo motor to a
sudden stop. Servo forced warning (AL.E6) occurs.

4) Forward rotation stroke end (LSP), reverse rotation stroke end (LSN) OFF

The droop pulse value is erased and the servo motor is stopped and servo-locked. It can be run in
the opposite direction.