Parameters – MITSUBISHI ELECTRIC MR-J2S- CP User Manual

Page 142

Advertising
background image

5 - 5

5. PARAMETERS


(2) Detail list

Class No. Symbol

Name and Function

Initial
value

Unit

Setting

range

0 *STY

Command system, regenerative option selection

Used to select the command system and regenerative option.

Selection of command system (Refer to section 4.2)
0: Absolute value command system
1: Incremental value command system
2: Absolute value command/incremental
value command specifying system

0

0

Selection of regenerative option
(Refer to section 14.1.1)
0: Not used (The built-in regenerative resistor is used.
However, the MR-J2S-10CP does not have a built-in
regenerative resistor and therefore cannot use it.)
1: FR-RC, FR-BU2
2: MR-RB032
3: MR-RB12
4: MR-RB32
5: MR-RB30
6: MR-RB50 (Cooling fan is required)
8: MR-RB31
9: MR-RB51 (Cooling fan is required)
If the regenerative option selected is not for use with the
servo amplifier, parameter error occurs

0000

Refer

to

Name

and

function

column.

B

asi

c pa

ra

met

ers

1 *FTY

Feeding function selection

Used to set the feed length multiplication factor and manual pulse generator

multiplication factor.

ST1 coordinate system selection
(Refer to section 4.2.2 to 4.2.4)
0: Address is incremented in CCW direction
1: Address is incremented in CW direction

Feed length multiplication factor (STM)
(Refer to section 4.2.2 to 4.2.4)
0: 1 time
1: 10 times
2: 100 times
3: 1000 times
Manual pulse generator multiplication factor
(Refer to section 4.3.2)
0: 1 time
1: 10 times
2: 100 times

Servo-on (SON) -off, forced stop (EMG) -off
follow-up for absolute value command
in incremental system or absolute value command/
incremental value command specifying system
0: Invalid
1: Valid
Normally, when this servo amplifier is used
in the absolute value command method of the
incremental system, placing it in a servo off or
forced stop status will erase the home position.
When "1" is set in this parameter, the home
position will not be erased if the servo amplifier
is placed in a servo off or forced stop status.
Operation can be resumed when servo-on (SON)
is turned on again or forced stop (EMG) is canceled.

0000

Refer

to

Name

and

function

column.