14. OPTIONS AND AUXILIARY EQUIPMENT


(4) Connection of the regenerative option

POINT

When the MR-RB50 MR-RB51 is used, a cooling fan is required to cool it.

The cooling fan should be prepared by the customer.

The regenerative option will generate heat of about 100 . Fully examine heat dissipation, installation
position, used cables, etc. before installing the option. For wiring, use flame-resistant cables and keep
them clear of the regenerative option body. Always use twisted cables of max. 5m (16.4ft) length for
connection with the servo amplifier.

(a) MR-J2S-350CP or less

Always remove the wiring from across P-D and fit the regenerative option across P-C.
The G3 and G4 terminals act as a thermal sensor. G3-G4 is opened when the regenerative option
overheats abnormally.

Servo amplifier

Regenerative option

Always remove the lead from across P-D.

D

P

C

G4

G3

(Note 2)

5m (16.4 ft) or less

Cooling fan(Note 1)

C

P

Note 1. When using the MR-RB50, forcibly cool it with a cooling fan (92 92, minimum air flow : 1.0m

3

).

2. Make up a sequence which will switch off the magnetic contactor (MC) when abnormal heating occurs.
G3-G4 contact specifications
Maximum voltage: 120V AC/DC
Maximum current: 0.5A/4.8VDC
Maximum capacity: 2.4VA

For the MR-RB50 install the cooling fan as shown.

82.5

40 (1.58)

82.5

13

3

Cooling fan installation screw hole dimensions

2-M3 screw hole
(for cooling fan installation)
Depth 10 or less
(Screw hole already

machined)

Cooling fan

Terminal block

Thermal relay

Installation surface

Horizontal installation

Vertical

installation

Top

Bottom

(3

.2

5

)

(5.

24)

(3.25)

[Unit : mm(in)]