14. OPTIONS AND AUXILIARY EQUIPMENT


14.2.2 Circuit breakers, fuses, magnetic contactors

Always use one circuit breaker and one magnetic contactor with one servo amplifier. When using a fuse
instead of the circuit breaker, use the one having the specifications given in this section.

Fuse

Servo amplifier

Circuit breaker

Class

Current [A] Voltage [V]

Magnetic contactor

MR-J2S-10CP(1) 30

frame

5A

K5

10

MR-J2S-20CP 30

frame

5A

K5

10

MR-J2S-40CP 20CP1

30 frame 10A

K5

15

MR-J2S-60CP 40CP1

30 frame 15A

K5

20

MR-J2S-70CP

30 frame 15A

K5

20

MR-J2S-100CP

30 frame 15A

K5

25

S-N10

MR-J2S-200CP

30 frame 20A

K5

40

S-N18

MR-J2S-350CP

30 frame 30A

K5

70

S-N20

MR-J2S-500CP

50 frame 50A

K5

125

S-N35

MR-J2S-700CP 100

frame

75A

K5

150

250AC

S-N50


14.2.3 Power factor improving reactors

The input power factor is improved to be about 90%. For use with a 1-phase power supply, it may be
slightly lower than 90%.

W

W1

C

RX S Y T Z

H

5(

0.

2)

D1

Installation screw

D

5(0.

2)

[Unit : mm]
([Unit : in.])

3-phase

200 to 230VAC

NFB

FR-BAL

R

S

T

X

Y

Z

L

1

L

2

L

3

MC

1-phase

230VAC

NFB

FR-BAL

R

S

T

X

Y

Z

L

1

L

2

L

3

MC

1-phase

100 to120VAC

NFB

FR-BAL

R

S

T

X

Y

Z

L

1

L

2

MC

(Note)

Servo amplifier
MR-J2S- CP

Servo amplifier
MR-J2S- CP

Servo amplifier
MR-J2S- CP

Note. Connect a 1-phase 230VAC power supply to L

1

/L

2

and keep L

3

open.