Parker Hannifin Dynaserv G2 User Manual

Page 160

Advertising
background image

70

Analog monitor selection

Always

Minimum value: 0
Maximum value: 5
Initial value:

4

Unit:

None

Long:

Short:

AnalogMonitorSelect

A_MonSel

Select the content to be output to the analog monitor.

0: Position deviation [pulse]
1: Test operation response [pulse]
2: Position command value [pulse]
3: Current position value [pulse]
4: Position command differential value (command velocity) [pps]
5: Current position differential value (current velocity) [pps]

71

Axis positioning error monitoring gain (analog monitor)

Always

Minimum value: 0
Maximum value: 8
Initial value:

0

Unit:

None

Long:

Short:

PerrMonitorGain

PerrMon_G

Specify the position deviation monitoring gain of the analog monitor.

0: 6.55V / 32768 pulses
1: 6.55V / 16384 pulses
2: 6.55V / 8192 pulses
3: 6.55V / 4096 pulses
4: 6.55V / 2048 pulses
5: 6.55V / 1024 pulses
6: 6.55V / 512 pulses
7: 6.55V / 256 pulses
8: 6.55V/ 128 pulses

72

Test operation monitoring gain (analog monitor)

Always

Minimum value: 0
Maximum value: 8
Initial value:

0

Unit:

None

Long:

Short:

TestMonitorGain

PerrMon_G

Specify the test operation response monitoring gain of the analog monitor.

0: 6.55V / 32768 pulses
1: 6.55V / 16384 pulses
2: 6.55V / 8192 pulses
3: 6.55V / 4096 pulses
4: 6.55V / 2048 pulses
5: 6.55V / 1024 pulses
6: 6.55V / 512 pulses
7: 6.55V / 256 pulses
8: 6.55V/ 128 pulses