6-10

Control Interfaces

6

6.5.7

Servo ON SERVO

The SERVO servo ON input signal is set to servo ON when the status is 1. In addition to this instruction, the
actual Servo ON/OFF status is affected by the setting of the SRV DS Servo ON disable switch on the front panel.
See the table below.

Servo ON/OFF

SERVO

SRV DS Servo ON

disable on the front panel

Actual servo status

Disabled

Status 0

Enabled

Disabled

Servo OFF

Status 1

Enabled

Servo ON

6.5.8

Current Limit Input

The current limit analog input signal gives a current limit from 0 to 100%, in proportion to a voltage input of 0 to
10V given by the external source. To enable this function, enable the #206 Enabling current limit external
input
parameter. This parameter has been disabled by factory default setting.