Control interfaces, 3 electrical specifications – Parker Hannifin Dynaserv G2 User Manual

Page 78

Advertising
background image

6-4

Control Interfaces

6

6.1.3 Electrical

specifications

[Interface power supply inputs]

COMP1, COMN1

Input the interface power supply for contact inputs and contact outputs.

Interface type name

SA

SB

Rated voltage

12 to 24 VDC (

±10%)

50VCD (

±10%)

[Contact inputs]

IN_ERR_RESET, IN_SERVO, IN_MODE_START, IN_ABORT, IN_MODE.0, IN_MODE.1,
IN_POSW.0, IN_POSR.1, IN_GAIN, IN_FN, IN_PLS_DIRECT, IN_PACT

Rated voltage

12 to 24 VDC (

± 10%)

Rated input current

4.1 mA/point (at 12 VDC)
8.5 mA/point (at 24 VDC)

Input impedance

3.0k

Operation voltage
(relative to COMP*)

At OFF 3.0VDC or less
At ON 9.0VDC or more

Allowable leak current

OFF is guaranteed at 1.0 mA or less

Input is ON while current flows into the photocoupler.

Vcc

470

COMP1

IN_*

1k

0.1

µF

PS2805

SA:2.7k

SB:1k

100k

Interface type name

SA

SB

4.0 mA/point (at 5 VDC)

5 VDC (

± 10%)

1.0k

At OFF 1.0VDC or less
At ON 4.0VDC or more

[Contact outputs] OUT_DRDY, OUT_SRDY, OUT_BUSY, OUT_XOVL, OUT_OVER, OUT_COIN

Maximum load current

0.1A/point, 0.5 A/common

ON voltage

0.5VDC or less

Leak current at OFF

0.1mA or less

Output is ON while the output transistor is ON.

PS2805

COMP1

OUT_*

COMN1

10k

MA8330

MA8330

2SD1820A

Vcc

1.5k

SA:8.2k

SB:1k

SA

SB

Rated voltage

12 to 24 VDC (

± 10%)

Interface type name

5 VDC (

± 10%)

[Position command pulse inputs]

PUA_IN

±

, SDB_IN

±

Connect a differential type line driver conforming to the RS422A standard, which is equivalent to AM26LS31.
(There is also an open collector specification. Please contact our sales department for more details.)

Input is ON when the (+) terminal has a
higher voltage than the (-) terminal, and
current flows into the photocoupler

Equivalent to

AM26LS31

TLP115A

33

91

470pF

470

Vcc

Controller

+

-

[Position current pulse outputs]

UA_OUT

±

, DB_OUT

±

, Z_OUT

±

Connect a differential type line receiver conforming to the RS422A standard, which is equivalent to AM26LS32.

Output is ON when the (+) terminal has
a higher voltage than the (-) terminal

Equivalent to

AM26LS32

AM26LS31

+

-

Controller