GEK-85718

EXTERNAL FAILURE (OH2)

Is the connection

YES

between THR and CM

correct and intact?

NO

Is the alarm function of

the external equipment

working properly?

Is ambient temperature

for the external

equipment within the

specified value?

Correct the ambient

condition to make it

within the specified

value.

YES

Are external thermal

sensors working

YES

thermal sensors.

Reduce the load of the

external equipment or

decrease the duty

cycle, or use

larger HP

The inverter will trip on

Remove RUN

OH2 if powered-up with

mand and press

a RUN command

RESET on the keypad

present. This is a

to clear the trip.

feature.

YES

RUN command from
remote conflicts with

STOP command from

Use shielded and

twisted wire for

control inputs. (Do not

connect terminals 11 or

CM to earth ground.)

was present (FWD or

Was STOP pressed on

the keypad when the

inverter was running

the

NO

Potential noise

at THR or CM

terminals .

YES

Possible invetter

failure Contact

fnverter Supplier

NO

YES

I

Check that proper

noise prevention

measures have

been taken.

Figure 8-8. “EXTERNAL FAILURE” TROUBLESHOOTING CHART