AF-300C

GEK-85716

OVERHEAT

I

Is the inverter cooling

NO

Check Power to

Correct Power

fan working?

cooling fan.

Supply Problem.

twisted wire for

YES

Replace Cooling Fan.

control inputs. (Do not

connect terminals 11 or

Is the

air

YES

passage plugged?

Remove obstacles.

NO

Is ambient temperature

YES

Check Speed Pot

within specified value?

wiring.

NO

YES

N O

Check that proper

noise prevention

measures have

YES

been taken.

I

Potential noise

interference.

Figure 8-4.

OVERHEATS” TROUBLESHOOTING CHART

CPU ABBNORMAL

Display abnormal

or out

YES

Turn power OFF, then

Sack ON (after CHARGE

lamp goes out).

Use shielded and

twisted wire for

control inputs. (Do not

connect terminals 11 or

CM to earth ground.)

Has data been

YES

The inverter is normal;

N O

Check that proper

played on indicator?

allow continuous

noise prevention

operation.

measures have

YES

NO

been taken.

Check that insertion of

Potential noise

CPU into IC socket is

interference.

YES

Possible inverter

correct.

failure Contact

I

lnverter Supplier

Figure 8-5. “CPU ABNORMAL” TROUBLESHOOTING CHART

8-7