CAUTION: If it is desired to use thermal interlocks, remove the
jumper from between terminals THR and CM, and connect nor-
mally closed thermal interlock contacts in series between
and CM.
Figure 5-8. KEYPAD PANEL OPERATION CONNECTIONS
Forward
Reverse
*FWD-CM and
terminals arre both ignored.
WARNING MECHANICAL MOTION HAZARD:
When running from the Keypad Panel with the “Local/Remote’ switch in the ‘Local” position,
pressing the FWD or REV key will cause the motor to rotate. Any RUN permissives that may be wired
to the FWD or REV terminals are ignored.
Figure 5-9. KEYPAD PANEL ‘RUN’ OPERATION EXAMPLE