Function 36 Frequency At Reference (FAR)

I

This signal is active (On) when the output fre-

quency reaches the reference frequency.

This is an open collector output.

If the optional relay unit is used, this signal can be
used as a contact output.
FAR: 0.5 to 5.0 Hertz

Starting Actions

Function 37 Starting Frequency

Function 36 Start Frequency Hold Time

Starting frequency set range is 0.5 to 5 Hz.

-- Starting frequency holding time setting range is

0.0 to 10 sec.

A starting frequency and holding time can be set
that is suitable for the starting torque
tics of the load. (Setting is ignored during decelera-
tion and reverse operation.)

Frequency Jump

These functions are used to avoid the natural

mechanical vibration of the load.

Three jump frequencies can be set.

are not active during acceleration and decel-

eration or if the multi-step speed settings are used.

The jump frequency range is adjustable between 0

to 5 Hz. (When the jump frequency is not used, set

it to ‘0.0’.

Jump 1, Jump 2, &Jump 3:

to 400 Hz

Number of Electric Motor Poles
Speed Conversion Coefficient.

Function 3d Number of Motor Poles
Function 3E Machine Speed Conversion

Coefficient.

These Function Codes are set to monitor the syn-
chronous speed of the motor and the machine
speed.

0

Time

100%

Function

Ranae

3d

2, 4, 6, 8, IO, 12

3E

0.1 10.0

Machine Speed = (Motor Synchronous Speed) X
(Machine Speed Conversion Coefficient).