Table 2: terminal identification/function – GE Industrial Solutions AF-300C AC Drive User Manual
Page 42
AF-300C
GEK-85716
TABLE 2: TERMINAL IDENTIFICATION/FUNCTION
Terminal
Label
Terminal
Name
Function
MAIN
CIRCUIT:
L3
AC Supply Line
Input Terminals
Connection for commercial power
VAC
60 Hz) or
(380-460 VAC 50 Hz).
lnverter Output
Terminals
Connection for
induction motor.
Brake
Unit Terminals
Connection for brake unit (optional). (Brake resistor must be
connected through brake unit.)
To be connected when power factor improving DC Reactor
(optional on 75 HP and below) is used. (Provided and required on
100 HP and above.)
P,
DC Reactor
Connection Terminals
Ground Terminal
Connection for ground.
CONTROL
POWER:
RO, TO
Control Power
Auxiliary Input
Connection for single-phase AC power for backing up the
control circuit power when input starter is used (460 VAC).
FREQ. SET
MONITOR
11
Frequency Setting
Common
Common terminal for frequency setting signals (terminals
12, 13,
and Cl). (Speed Pot Common)
12
Frequency Setting
Voltage Input
When 0 to +
VDC is input, the maximum frequency is
reached at
0 VDC. The output frequency is proportional
down to 0 VDC. Input impedance is 22K ohm. (Speed Pot Wiper)
13
Frequency Setting
Voltage Output Term.
+
VDC power supply for Speed Pot (1
maximum).
(Speed Pot Power)
Cl
Frequency Setting
Current Input
When 4 to 20mA DC is input, the maximum frequency is reached at
20mA. The output frequency is proportional down to 4mA.
Vi
Voltage Input
Auxiliary Terminal
Reaches maximum output frequency at
0 VDC (the output
freq. is proportional down to 0 VDC). Input impedance is 22K ohms.
FM1
FM2
Frequency Meter
Connection Points
Provides an output of 0 to
VDC
VDC at max. frequency).
Available for connection of a voltmeter (with internal resistance of
1 OK ohms). FM1 = Pos., FM2 = Neg. To output a digital signal,
SW2 must be changed to 2-3 position. (See Figure 4-9 and
Function Codes 40 and 50.)
4-10