Figure 4-7. GROUND CONNECTIONS

GROUND TERMINAL CONNECTIONS

CONTROL CIRCUIT WIRING

It is necessary to provide grounding in order to pro-

tect against an electral shock due to leakage and to

reduce the effects of electrical ‘noise”. (See Figure

Preferably, each inverter or other piece of equipment

should be grounded individually. If this is not pos-
sible, the alternative method is common grounding
where the ground wire from each piece of equipment
is connected at the ground point.

NOTE: The ground wire

be as large a gauge

as possible and the length should be kept as

as

possible.

Avoid grounding method where the ground wire is

used in common with other equipment i.e., do not
daisv chain around connections.

INVERTER CONTROL

CIRCUIT WIRING

I

C

I

R

C

U

I

T

W

I

R

I

N

G

CROSS AT RIGHT

ANGLE AND KEEP

KEEP NOT LESS

AT LEAST 1 INCH

Figure 4-8. CONTROL WIRE ROUTING

Perform all control wiring in accordance with the

following applicable subparagraphs (and referenced

Figures) and the applicable circuit as shown in Fig-
ures 4-15 to 4-26 (located at the end of this Section).
Refer to TABLE 2for terminal descriptions and TABLE

3 for wire sizing.

CAUTION:

reliabilitv contacts for lowvoltaqe

and current sianals must be used on the control

circuit terminals (FWD, REV, BX, THR,

PU, IL,

X2. X3,

, RT2,

When the contact is open,

the voltage is approximatelv

when the

contact is closed, the current is approximatelv 3

DC (see

4-12 for circuit).

CAUTION:

The control circuit terminal wirina should

be kept as far

as possible from the main power

wirinn to prevent operational error due to noise inter-
ference. Never install both

of wirinq in the same

duct or conduit. (A separation distance of 10 centi-
meters

inches1 or more is recommended.) If the

control circuit wirina must cross the main power
inn, it should cross at a riaht

and be seperated

at least

4-8).

CAUTION:

Use shielded twisted wire for the con-

trol circuit wirina; wirinn should be as short as

i.e. 20 meters

feet) or less. Connect shield

to the

terminal and leave the other

end open and

insulated.

CAUTION:

a suppressor in parallel with any

or

coils, etc. that mav be close to

the inverter.