GE Industrial Solutions AF-300C AC Drive User Manual

Page 34

Advertising
background image

RF-3 00c

POWER

INPUT

2

1

RC LINE

REACTOR

(IF REQU

CIRCUIT

CUSTOMER SUPPLIED

3

RC POWER

Figure 4-2. AC POWER CONNECTION

AUXILIARY CONTROL POWER SUPPLY

CONNECTION

When using the circuit shown in Figure 4-3, it is

necessary to connect terminals

and

to the

hot side of the MC Contactor.

CAUTION:

Do not

to make the RO and TO

connections. If not made, continuous

of the

MC Contactor

occur under certain conditions

that will stress (or fail) the

resistor and DC link

capacitors.

AC LINE REACTOR CONNECTION

An AC Line Reactor is required on

inverters

if the

rating of the supply transformer is greater

than

the horsepower rating of the inverter or

500 KVA (whichever is greater). This reactor is con-
sidered optional and must be purchased separately

when required for specific applications (see “Op-
tions’ paragraph in Section 2).

(CUSTOMER

SUPPLIED)

Figure 4-3. AUXILIARY CONTROL POWER SUPPLY CONNECTION

DETACH THE FACTORY

INSTALLED SHORT-CIRCUIT

(IF PRESENT)

,

.

N

DC

Figure 4-4. DC REACTOR CONNECTION

DC REACTOR CONNECTION

A DC Reactor is required on all

inverters

rated 100 HP and above. This reactor is included in

the purchase of the inverter and shipped with the

inverter. This reactor must be installed or the war-
ranty will be voided.

1. Remove the jumper between the

and

terminals (installed at factory).

2. Connect DC Reactor between these terminals as

shown in Figure 4-4 (see TABLE 3 for wire sizing).

4-2