GE Industrial Solutions AF-300C AC Drive User Manual
Page 34
RF-3 00c
POWER
INPUT
2
1
RC LINE
REACTOR
(IF REQU
CIRCUIT
CUSTOMER SUPPLIED
3
RC POWER
Figure 4-2. AC POWER CONNECTION
AUXILIARY CONTROL POWER SUPPLY
CONNECTION
When using the circuit shown in Figure 4-3, it is
necessary to connect terminals
and
to the
hot side of the MC Contactor.
CAUTION:
Do not
to make the RO and TO
connections. If not made, continuous
of the
MC Contactor
occur under certain conditions
that will stress (or fail) the
resistor and DC link
capacitors.
AC LINE REACTOR CONNECTION
An AC Line Reactor is required on
inverters
if the
rating of the supply transformer is greater
than
the horsepower rating of the inverter or
500 KVA (whichever is greater). This reactor is con-
sidered optional and must be purchased separately
when required for specific applications (see “Op-
tions’ paragraph in Section 2).
(CUSTOMER
SUPPLIED)
Figure 4-3. AUXILIARY CONTROL POWER SUPPLY CONNECTION
DETACH THE FACTORY
INSTALLED SHORT-CIRCUIT
(IF PRESENT)
,
.
N
DC
Figure 4-4. DC REACTOR CONNECTION
DC REACTOR CONNECTION
A DC Reactor is required on all
inverters
rated 100 HP and above. This reactor is included in
the purchase of the inverter and shipped with the
inverter. This reactor must be installed or the war-
ranty will be voided.
1. Remove the jumper between the
and
terminals (installed at factory).
2. Connect DC Reactor between these terminals as
shown in Figure 4-4 (see TABLE 3 for wire sizing).
4-2